Project

General

Profile

Run plan » History » Version 391

« Previous - Version 391/1482 (diff) - Next » - Current version
Pip Hamilton, 09/21/2017 05:07 PM


Run Plan

Contacts

Contact Number Alt Number
Shifter 1 (937) 582-6663 1(937) 5-UBOONE
Backup Shifter 1 (978) 822-2582 9788 BACK UB
RunCo (Kevin) 425-318-9990
Deputy RunCo (Pip) 224-253-2345

Link to which experts to call in case of other alarms

Run Configuration

Summary

On the weekend of the 22nd to the 24th, we will be performing a number of short detector studies + calibration runs. Shifters will be given instructions by the runco and by the experts in charge of each study. Study leads are as follows:

Zig-zag noise (Friday morning) - Mike Matulik
Calibration pulser run (Saturday) - Brian Kirby
DAQ tests - Yun-Tse Tsai

Outside active study periods (as defined by the experts), shifters should take one five-minute noise run every two hours, using run config 633.

Run Control

Configuration Config ID Time [min]
Zig-Zag Noise Run Configuration 633 5
ASIC config to unmask noise on FT6 630 5
ASIC config to return FT6 to normal operation 631 5

Configs 630 and 631 are misnamed and will be deleted after this period of works is over. They are not to be used for the 5 minute noise runs; only recorded here for posterity when we want to come out of the zig-zag testing configuration.

Notes on current operations:

  • MiniBooNE is down until 9/18.
    • Do not fill out the miniboone checklist.
  • We've been getting dewpoint alarms. The alarm limits are set more conservative than the cryo system's heater control. Therefore this is only a problem if the alarms persist for more than 30 minutes.
  • Similarly, the ZMON has been throwing frequent alarms. The relevant expert has been informed and investigations are ongoing.
  • While Jose is transferring SN data (he'll notify via the gchat), some seb*_memfree alarms may occur intermittently.
  • CRT Crate Rails alarms (uB_CrateRails_CRTUtil*) can be ignored until this line is removed from the run plan.
  • You may see major OnDetPower HIHI alarms from TPCPS_2_10_904 and 806. These are negative channels whose upper limits are set close to zero - with the wire bias off, small fluctuations in the readback around zero can put them into alarm. Feel free to acknowledge these when you see them; if they reappear it will be due to small fluctuations clearing the alarm state and then putting it back into alarm.

Additional Shifter Requirements:

  • Please follow the Shift_turnover procedures
  • At the end of your shift, please post a plot of the last 8 hours of variable: uB_Cryo_IFIX_1_0/PT102
  • During access to the detector:
    • Please fill out a Beginning of Detector Access and End of Detector Access Form.
    • If the "keytree" alarm occurs, and the persons accessing the platform have not called the shifter first, then call LArTF to find out who is accessing the detector. If no one answers, call the runco.
    • Detector platform access must be cleared by runcos.
    • At the end of detector access, please acknowledge the keybank incomplete alarm.

In Case of Cryo Alarms

All the cryo related alarms from either iFix or slow controls should be documented by shifters in ECL with the alarm variable names.

If a shifter does not receive a call within 15 minutes of seeing a MAJOR cryo alarm: