Project

General

Profile

Wiki » History » Version 222

Pawel Kryczynski, 02/28/2016 11:47 AM

1 104 Jennifer Raaf
!https:/redmine/attachments/download/17373/Lariat_Logo_256.jpg!  
2 104 Jennifer Raaf
 
3 218 Jason St. John
ROC West x5413
4 1 William Badgett
MCenter Control Room (MC-CR) x3726 or x8871
5 117 Jennifer Raaf
* Call the Main Control Room (x3721) at the start and at the end of shift. This is required, and pleasant.
6 69 Jason St. John
* If the beam goes away for more than a few spills, look for Accelerator Alarms in ACNET (a default window). If the problem persists a few minutes, and you see nothing about it in the MCR elog, (or you just really want to find out more), call the MCR.  They're friendly, though they may be super-busy.
7 25 William Badgett
8 150 Jason St. John
{{toc}}
9 63 Jason St. John
10 204 Luke Batten
11 147 Jason St. John
h1. Shifter Stuff
12 1 William Badgett
13 207 Luke Batten
* [[Before your first shift at LArIAT]]
14 202 Jason St. John
* [[LArIAT Run 2 Shifter Instructions]] (February 2016)
15 130 Jennifer Raaf
** [[Run Plan]]
16 192 Jennifer Raaf
** "LArIAT Expert Call List":http://lariat.fnal.gov/internal/internal.html  (User is "lariat", password same as docdb)
17 1 William Badgett
18 171 Jason St. John
h2. Link summary ( [[quick start]] )
19 166 Steven Dytman
20 197 Jason St. John
* "Accelerator Schedule":http://www-ad.fnal.gov/ops/schedule.html  (power outages, etc)
21 215 Luke Batten
* "LArIAT e-Log":http://dbweb0.fnal.gov:8080/ECL/lariat/E/index  For making/ending access, starting/ending shifts.
22 210 Luke Batten
* [[LArIAT DAQ Instructions]] (February 2016)
23 147 Jason St. John
* "LArIAT Run Status Webpage":http://nusoft.fnal.gov/lariat/run.html
24 196 Ryan Linehan
* "LArIAT Run Summary Webpage":http://lariat-wbm.fnal.gov/wbm/servlet/LariatRunSummary
25 213 Luke Batten
* "LArIAT Online DQM":http://lariat-dqm.fnal.gov (works with VPN or VNC or on-site only, for now)
26 164 Johnny Ho
* How to use the [[event viewers]]
27 165 Johnny Ho
* How to make [[DQM plots]] (may be outdated)
28 1 William Badgett
* "Synoptic":https://cdcvs.fnal.gov/redmine/projects/lariat-online/wiki/Using_Synoptic_for_monitoring
29 149 Jason St. John
* "Beam monitoring(ACNET directly)":https://redmine.fnal.gov/redmine/projects/lariat-online/wiki/Using_ACNET_for_monitoring?parent=Wiki
30 1 William Badgett
* "Accelerator Operations Elog":https://www-bd.fnal.gov/Elog/?logNames=Operations
31 1 William Badgett
* "MC7 WebCam":http://131.225.176.26/
32 1 William Badgett
33 151 Jason St. John
h3. Important knowledge
34 1 William Badgett
35 149 Jason St. John
* "List of MC7 ACNET devices":https://redmine.fnal.gov/redmine/projects/lariat-online/wiki/MC7_in_ACNET
36 149 Jason St. John
* [[MC-7 Enclosure Layout]]
37 1 William Badgett
* "In case the beam TVs are off":http://www-bd.fnal.gov/notifyservlet/www?project=&refresh=on&infolinks=top
38 1 William Badgett
* [[The LArIAT supercycle]] _How DAQ operations relate to the main injector supercycle_ 
39 151 Jason St. John
* "Hardware-Connections-and-Configurations":https://redmine.fnal.gov/redmine/projects/lariat-online/wiki/Wiki#Hardware-Connections-and-Configurations
40 151 Jason St. John
* "Electronic Hardware Documentation":https://redmine.fnal.gov/redmine/projects/lariat-online/wiki/Wiki#Electronic-Hardware-Documentation
41 132 Jason St. John
42 149 Jason St. John
h3. Obsolete links
43 1 William Badgett
44 202 Jason St. John
* [[LArIAT Run 1 Shifter Instructions]] (June 2015)
45 149 Jason St. John
* -LArIAT Engineering Run (Aug 2014) [[How to Run the Lariat Data Acquisition]]- (OBSOLETE)
46 1 William Badgett
* -"Shifter Instructions":https://docs.google.com/document/d/1mlN_UIOCqwhe0cFiU7mRc3-lxDZhY-4TmIy23rOzILI/pub August 2014- (Some obsolete information)
47 164 Johnny Ho
* -How to make [[Lariat DAQ Plots]]- (OBSOLETE)
48 149 Jason St. John
49 83 Jason St. John
h1. Troubleshooting 
50 1 William Badgett
51 152 Jason St. John
Any time day or night, please call experts if you are in need of help and the answer is not provided below.
52 152 Jason St. John
53 179 Jason St. John
h2. *Trouble getting started*
54 152 Jason St. John
55 205 Luke Batten
* If you cannot ssh to FTBFLX machines: Get a kerberos ticket for yourself: @kinit <yourKerberosPrincipal>@, then ssh ftbf_user@ftbflx18 (or ssh ftbf_user@ftbflx15 or ssh ftbf_user@ftbf-cr-03).
56 216 Luke Batten
* If your Kerberos username and password are good, but you can't log on to FTBFLX[NN] machines:  Have someone who CAN log into those machines check that your kerberos principal appears in @~ftbf_user/.k5login@ in the LArIAT section (email the Run Co-ordinator at stjohn@fnal.gov). 
57 216 Luke Batten
* The same ssh errors may also apply to computers at ROC West. Troubleshoot using the above methods.
58 1 William Badgett
59 152 Jason St. John
h2. *Trigger and DAQ system*
60 152 Jason St. John
61 188 Jason St. John
When the DAQ crashes, please post the relevant information to [[DAQerrors]] for experts to study.
62 188 Jason St. John
63 187 Jason St. John
h3. Common failures:
64 187 Jason St. John
65 187 Jason St. John
* DAQ fails with @ERROR: ReadRegisgter ACQUISITION_STATUS CAEN_DGTZ_CommError BoardId 0@  wait 2 minutes, then try to start again.
66 187 Jason St. John
** Try issuing the command @lariatReset 0 1@ waiting more then 5 seconds, and trying again.
67 187 Jason St. John
This command is appropriate when one sees any type of "CAEN_DGTZ" error.  This command will NOT help the persistent ports error.
68 187 Jason St. John
* DAQ fails with @Found persistent communication port still open@
69 187 Jason St. John
** Wait 8 minutes for the ports to clear, then try again.
70 222 Pawel Kryczynski
* DAQ fails with "An exception occurred when trying to send a message to ...".  Check that the terminal you are running the DAQ from is indeed lariat-daq00 (or a screen within it).  Output from @klist@ should show the default principal as "lariat/lariat/lariat-cr-02.fnal.gov@FNAL.GOV" or similar if running from a screen off lariat-daq00 from the ROC-West station.
71 187 Jason St. John
72 187 Jason St. John
h3. Other failures: 
73 187 Jason St. John
74 1 William Badgett
* If the DAQ is having trouble talking to the crates, try issuing the command @lariatReset 0 1@ waiting more then 5 seconds, and trying again.
75 187 Jason St. John
This command is appropriate when one sees any type of "CAEN_DGTZ" error.  This command will NOT help the persistent ports error.
76 187 Jason St. John
* If the trigger crate has been power cycled and the V1495 is not emitting triggers: [[Reset1495]]
77 83 Jason St. John
78 152 Jason St. John
h2. *Wire Chambers*
79 152 Jason St. John
80 162 Jason St. John
* If the wire chambers are acting strangely: "remote power cycling instructions":https://redmine.fnal.gov/redmine/projects/lariat-online/wiki/Communicating_with_the_wire_chambers including mini-DAQ and telnet interface.
81 135 Jason St. John
* If the wire chamber system is skipping spill numbers, it may be a high trigger rate (> 30 k per spill).  The wire chamber controller may still be reading out the hits from the last spill.
82 83 Jason St. John
83 172 Jason St. John
h2. Power Cycle the ASICs (TPC Wire Noise)
84 168 William Badgett
85 168 William Badgett
* Anecdotal evidence has shown that analog noise on the TPC wire readout channels can be 
86 169 William Badgett
alleviated by power cycling the TPC electronics: ASICs and Warm Receiver/Drivers
87 203 Will Foreman
* You can remotely power cycle the TPC electronics.  Log onto lariat-gateway00.fnal.gov with X-forwarding enabled, type "firefox", and go to http://lariat-pdu02.fnal.gov.  Usename "ftbf" (password posted on whiteboard in MC7).  Choose the *CYCLE* option, which will automatically give a 60 
88 173 William Badgett
second powerless interlude.
89 173 William Badgett
* Further important informations can be found on the white board in MC-CR.
90 168 William Badgett
* This mechanism is controlled by a smart power distribution unit (PDU) located under the 
91 168 William Badgett
TPC electronics power supply near the cryostat in the enclosure.   Due to electrical safety 
92 170 William Badgett
rules you must *NOT* use any of the other outlets on this PDU.  Do *NOT* remove the protective 
93 168 William Badgett
outlet covers at any time.
94 177 William Badgett
!https://redmine.fnal.gov/redmine/attachments/download/25467/lariat-pdu02-cycle.png!
95 174 William Badgett
96 181 Jason St. John
h2. Recover from a LAr level interlock
97 181 Jason St. John
98 182 Jason St. John
Assuming the LAr Level dropped low enough to trip off the TPC Cathode power supply, and maybe you even powered down the PMTs.
99 182 Jason St. John
100 181 Jason St. John
# Be sure HV is set to zero for these: Cathode Drift, Wire Bias, cryo-PMTs
101 183 Sarah Lockwitz
How to control the [[Drift HV]]
102 181 Jason St. John
# Power down the ASICs. (They should be off when TPC voltages change.)
103 181 Jason St. John
# Bring up the Cathode
104 181 Jason St. John
# Bring up the Wire Bias
105 181 Jason St. John
# Bring up the ASICs
106 181 Jason St. John
# Bring up the PMTs
107 181 Jason St. John
108 217 Flor de maria Blaszczyk
h2. VME power supplies known issues (controlled from Synoptic / ACNET)
109 217 Flor de maria Blaszczyk
110 219 Flor de maria Blaszczyk
"Detailed instructions for controls via Synoptic":https://cdcvs.fnal.gov/redmine/projects/lariat-online/wiki/Using_Synoptic_for_monitoring#section-10
111 220 Flor de maria Blaszczyk
*ONLY IF THE ABOVE DOESN'T WORK* 
112 220 Flor de maria Blaszczyk
"Instructions for controls via ACNET":https://cdcvs.fnal.gov/redmine/projects/lariat-online/wiki/Using_ACNET_to_power_up_the_power_supplies
113 219 Flor de maria Blaszczyk
114 220 Flor de maria Blaszczyk
* The readback voltage doesn't make any sense, is of the wrong polarity and/or is way above the nominal value, but just for a fraction of time.
115 220 Flor de maria Blaszczyk
This is most likely just a glitch in the readout, please ignore if it happens once or twice. If it happens too frequently, set voltage to 0, turn off the power supply and report it. 
116 219 Flor de maria Blaszczyk
117 220 Flor de maria Blaszczyk
* The readback voltage doesn't make any sense, is of the wrong polarity and is way above the nominal value, and the value is stable~ish (you might see small fluctuations over time)
118 220 Flor de maria Blaszczyk
This is a typical symptom of a bad power supply. Try to set it back to 0, turn it off and disconnect the SHV cable. If the readout values remain the same, it confirms there is a hardware problem. Please contact Brian Fellenz for repairs if we don't have a spare for that unit.
119 1 William Badgett
120 220 Flor de maria Blaszczyk
FYI, the power supplies have a given voltage rating and cannot physically deliver voltages beyond that range. Also, their polarities cannot be swapped so if you see the wrong sign on the readout ie a positive voltage on a negative power supply or vice versa, then you can be sure the unit is broken or you have a problem somewhere else in the system.
121 221 Flor de maria Blaszczyk
- Bias voltage rating: - 500 V for the shield and induction planes, + 500 V for the collection plane.
122 221 Flor de maria Blaszczyk
- ELT and Hamamatsu PMTs: +2000 V
123 221 Flor de maria Blaszczyk
- All of the other units: -2000 V
124 220 Flor de maria Blaszczyk
125 219 Flor de maria Blaszczyk
* Something went wrong during a ramp, I need to turn off the supply!
126 220 Flor de maria Blaszczyk
There is an interlock that prevents you from using the normal fast controls on the power supply when a ramp is on-going. First, *stop the ramp by clicking on the STOP button*. This will stop the ramp and clear the interlock. If you need to go back to 0 quickly, use the fast controls to set the voltage to 0 and *don't forget to turn off the supply!*
127 219 Flor de maria Blaszczyk
128 221 Flor de maria Blaszczyk
*Even if the controls appear not to respond, set the voltage to 0 and turn the supply off*. Contact Charlie Briegel first and describe the problem in detail. If you can and if it's safe, disconnect the SHV cable from the power supply. If the readback values remain the same, then the power supply is broken.
129 219 Flor de maria Blaszczyk
130 219 Flor de maria Blaszczyk
* ACNET controls expert: Charles (Charlie) Briegel, x4510 briegel@fnal.gov  
131 219 Flor de maria Blaszczyk
* VME power supplies repairs / replacements: Brian Fellenz, x2512 fellenz@fnal.gov
132 219 Flor de maria Blaszczyk
133 217 Flor de maria Blaszczyk
h2. Synoptic troubleshooting
134 217 Flor de maria Blaszczyk
135 217 Flor de maria Blaszczyk
%{color:red}"Synoptic Troubleshooting":https://cdcvs.fnal.gov/redmine/projects/lariat-online/wiki/Using_Synoptic_for_monitoring#Troubleshooting%
136 217 Flor de maria Blaszczyk
137 217 Flor de maria Blaszczyk
138 68 Michael Kordosky
h1. Hardware Connections and Configurations
139 1 William Badgett
140 141 William Badgett
* [[TPC Channel Mapping]]
141 51 Jason St. John
* [[Non-TPC Detectors]] *Naming and numbering in MC7*
142 133 Jason St. John
* "Cable Patch Panel Spreadsheet":http://goo.gl/JXiH8Y
143 54 Jason St. John
* [[Connections on the Control Room Patch Panel]]
144 54 Jason St. John
145 51 Jason St. John
* [[Logical inputs to the CAEN V1740]]
146 51 Jason St. John
* [[Connections into the WUT TDC]]
147 51 Jason St. John
* [[Connections into the V1751 Digitizer]]
148 1 William Badgett
* [[Trigger inputs|Connections in/out of the V1495 Trigger]]
149 68 Michael Kordosky
* [[Logic pulse widths and discriminator thresholds]]
150 68 Michael Kordosky
* [[WUT configuration]]
151 74 William Badgett
* [[Timing of ACnet TCLK Events]]
152 140 William Badgett
* The [[Teensy]] LAr ASIC controller's configuration
153 50 Michael Kordosky
154 138 Roberto Acciarri
* [[Punch Through counters voltages and rates ]]
155 138 Roberto Acciarri
156 102 Jason St. John
h1. Electronic Hardware Documentation
157 45 Michael Kordosky
158 51 Jason St. John
* Link to LArIAT eLog http://dbweb0.fnal.gov/ECL/lariat
159 51 Jason St. John
* [[LariatOnlineGit]] Accessing the LArIAT Online GIT repository
160 98 Brian Rebel
* [[Building LArIATOnline with CMake]]
161 44 Michael Kordosky
162 51 Jason St. John
* [[LArIAT TPC Readout Parameters]]
163 185 William Badgett
* [[LArASIC Preamp Documentation from BNL]]
164 51 Jason St. John
* [[LArIAT DAQ Commercial Products]] Technical Documentation and Firmware Files
165 101 William Badgett
* [[LArIAT CAEN Products]] Technical Documentation and Firmware Files
166 51 Jason St. John
* Test Beam Wire Chamber Sten Hensen's [[TDC Readout Documentation]]
167 89 William Badgett
* WUT Wave Union TDC: [[Jinyuan's TDC Documentation]]
168 51 Jason St. John
* [[v1495 notes]] Notes and working area for the V1495 and V2718
169 195 Johnny Ho
* [[A3818 PCI optical controller]] links
170 35 Michael Kordosky
171 1 William Badgett
* [[DAQ Configuration]] settings, parameters, starting a run
172 51 Jason St. John
* [[Raw Data Format and Readout Source code]]
173 100 John Freeman
* [[All things lariat-artdaq]] (UPDATED 11/5/14)
174 154 Jason St. John
* [[Interpreting Wire Chamber TDC Data]]
175 36 Michael Kordosky
176 54 Jason St. John
* [[LArIAT Test Stand]] Photographs
177 47 Michael Kordosky
178 72 Michael Kordosky
h1. Diagnostic and Control Software
179 72 Michael Kordosky
180 73 Michael Kordosky
_Test programs in the_ lariat-online/daq/src _directory_
181 73 Michael Kordosky
182 72 Michael Kordosky
* [[DumpDigitizerData]]
183 72 Michael Kordosky
* [[SummarizeDAQOutput]]
184 72 Michael Kordosky
* [[Reset1495]]
185 72 Michael Kordosky
* [[ScalarReadout]]
186 97 Pawel Kryczynski
* [[Data_quality_monitoring_module]]
187 72 Michael Kordosky
188 139 William Badgett
* CAEN's [[WaveDump]] utility
189 139 William Badgett
190 75 Jason St. John
h1. Examining the WC mini DAQ ASCII data
191 75 Jason St. John
192 75 Jason St. John
The Processor makes TTrees from the ASCII files saved by @mc7-daq.py@
193 82 Jason St. John
[[WC MiniDAQ Data Processor]]
194 75 Jason St. John
195 153 Jason St. John
h1. Data Files from the year 2013
196 76 Will Flanagan
197 85 William Badgett
Data files for various beam conditions can be found in the [[DataFiles]] page.
198 85 William Badgett
199 51 Jason St. John
h1. Meetings
200 51 Jason St. John
201 51 Jason St. John
* [[Connecting to LArIAT ReadyTalk]]
202 198 Johnny Ho
203 1 William Badgett
h1. Miscellaneous
204 198 Johnny Ho
205 216 Luke Batten
* The control room shifter computer (MCenter) can be logged into as ftbf_user@ftbflx18.fnal.gov after passing through lariat-gateway.fnal.gov
206 198 Johnny Ho
* [[Proxy using SSH tunnel]]