Bug #9037

Relax the MINOR High/low alarm range on TPCPS LV modules 1 through 6

Added by Sowjanya Gollapinni almost 4 years ago. Updated almost 4 years ago.

Status:
Closed
Priority:
Normal
Category:
slow monitoring and control
Start date:
06/04/2015
Due date:
% Done:

100%

Estimated time:
Spent time:
Duration:

Description

Relax the alarm ranges on MaxSenseVOLT_RW for TPCPS LV modules 1 to 6. Variables listed below:
uB_OnDetPower_TPCPS_1_x/MaxSenseVOLT_RW (here x ranges from 0 to 7)
uB_OnDetPower_TPCPS_2_x/MaxSenseVOLT_RW (here x ranges from 100 to 107)
uB_OnDetPower_TPCPS_3_x/MaxSenseVOLT_RW (here x ranges from 200 to 207)
uB_OnDetPower_TPCPS_4_x/MaxSenseVOLT_RW (here x ranges from 300 to 307)
uB_OnDetPower_TPCPS_5_x/MaxSenseVOLT_RW (here x ranges from 400 to 407)
uB_OnDetPower_TPCPS_6_x/MaxSenseVOLT_RW (here x ranges from 500 to 507)

Probably changing the Minor (high/low) alarm to 3.3 or 3.2 will remove the above ~50 alarms!

History

#1 Updated by Glenn Horton-Smith almost 4 years ago

  • Category set to slow monitoring and control
  • Status changed from New to Resolved
  • % Done changed from 0 to 100

Values adjusted.

After discussion, Sowjanya and I decided to set LOW = LOLO = 3.35 V on these channels.
Our rationale is that lowering the MaxSenseVoltage below 3.35 V on a 3.3V channel is asking for trips, so we want extra warning if this setting gets into that state.

Also, we have set HIGH = HIHI = 4.0 on these channels. Note this is just the alarm level on the setting of the MaxSenseVoltage setting, not the MaxSenseVoltage itself. The MaxSenseVoltages are currently set to 3.4 V.

#2 Updated by Glenn Horton-Smith almost 4 years ago

  • Status changed from Resolved to Closed