Milestone #4841

PDU Setup

Added by Bonnie King over 6 years ago. Updated about 6 years ago.

Status:
Closed
Priority:
Normal
Assignee:
Start date:
10/24/2013
Due date:
11/06/2013
% Done:

100%

Estimated time:
Spent time:
Experiment:
MicroBooNE
Duration: 14

Description

Configure PDUs in LArTF. Need power-on sequencing and trip limits.

History

#1 Updated by Bonnie King over 6 years ago

  • Assignee set to Bonnie King

From Linda:

According to NEC code, 15A circuits can run continuous at 80% max or 12A.
I would set the warning at 11.5A, alarm at 12.5A to allow for momentary spikes.

EVB first, as Eric mentions, with a 2 minute delay. Since SEB 9 and 10 are powered by the same PDU, power them next.
Then I would start powering up the SEBs in order, 1-8, with a time delay that allows the current to settle.
You just want to get over the initial current surge before powering up the next unit.
Lastly, turn on PDU-4 machines with the same delay defined by the duration of surge current.

Linda

port delay(sec)

Sent the following proposal to Linda:

PDU 1 and 2:

1- ubdaq-prod-seb01:1       120
2- ubdaq-prod-seb02:1 130
3- ubdaq-prod-seb03:1 140
4- ubdaq-prod-seb04:1 150
5- ubdaq-prod-seb05:1 160
6- ubdaq-prod-seb06:1 170
7- ubdaq-prod-seb07:1 180
8- ubdaq-prod-seb08:1 190

PDU3:

1- ubdaq-prod-seb09:1       120
2- ubdaq-prod-seb09:2 120
3- ubdaq-prod-seb10:1 130
4- ubdaq-prod-seb10:2 130
5- ubdaq-prod-evb:1 0
6- ubdaq-prod-evb:2 0

PDU4:

1- ubdaq-prod-ws02          130
2- ubdaq-prod-ws01 140
6- ubdaq-prod-ipmi 0
7- undaq-prod-near1:1 120
8- ubdaq-prod-near1:2 120

#2 Updated by Bonnie King over 6 years ago

  • % Done changed from 0 to 100

#3 Updated by Bonnie King over 6 years ago

  • Status changed from New to Resolved

#4 Updated by Bonnie King about 6 years ago

  • Status changed from Resolved to Closed