Project

General

Profile

Task #19608

Milestone #20350: IOTA BPM deployment

Milestone #19607: IOTA ACNET Interface

Crate status and control device

Added by John Diamond over 1 year ago. Updated 9 months ago.

Status:
Work in progress
Priority:
Normal
Start date:
04/09/2018
Due date:
% Done:

80%

Estimated time:
24.00 h
Spent time:
Duration:

Description

This device will give status about the crate hardware and the status of bpmd.

History

#1 Updated by John Diamond over 1 year ago

Recommended device naming pattern: x:BPMyyy
  • yyy = three digit crate identifier
Reading property:
  • Structured data with 4 byte elements unsigned integers
    • [0] = bpmd uptime counter (number of seconds)
    • [1] = bpmd pid
    • [2] = number of DAQ modules present
    • [3] = integer representation of the DAQ state
    • [4] = number of BPMs configured
    • [5] = integer representation of the state machine type
    • [6] = state machine cycle counter
    • [7] = most recent state machine cycle identifier
Setting property:
  • none
Status property:
  • Bit 0: bpmd is running
  • Bit 1: Timing signal generator is present
  • Bit 2: Clock decoder is present
  • Bit 3: DAQ modules are ready
  • Bit 4: DAQ modules are armed
  • Bit 5: DAQ modules are triggered
  • Bit 6: State machine is enabled
  • Bits 19-31: DAQ module present in slot n
Control property:
  • 0: start bpmd
  • 1: shutdown bpmd
  • 2: restart bpmd
  • 3: enable state machine
  • 4: disable state machine

#2 Updated by John Diamond over 1 year ago

  • Estimated time set to 24.00 h
  • Parent task set to #19607

#3 Updated by John Diamond over 1 year ago

  • Status changed from New to Assigned
  • Assignee set to Elliott McCrory

#5 Updated by John Diamond over 1 year ago

To clarify:
  • [5] = integer representation of the state machine type
    • Use MachineContext::machineGet() and cast the FNALMachine to an unsigned int
  • [7] = most recent state machine cycle identifier
    • This is just my confusing way of saying the TCLK cycle reset ID. Use MachineContext::resetTCLKGet().

#6 Updated by Elliott McCrory 9 months ago

  • Status changed from Assigned to Work in progress
  • % Done changed from 0 to 80

There is an outstanding problem with setting some control bits at IOTA. However, we believe that this is not a problem in the front end. See logbook entry: https://www-bd.fnal.gov/Elog/?orEntryId=141937