Changes requested by Ben Carls per review committee recommendations:

  1. Turn the age of data from a MAJOR alarm to a MINOR alarm, warranting an email only.
  2. Change minor alarm threshold to 6 hours. (No major alarm.)
  3. Create an alarm for QA/QC from the long purity monitor:
    QAQCRATIO = ANODETRUE / CATHTRUE
    Initially, an alarm should go off if the ratio goes below 0.391.

History

#1 Updated by Glenn Horton-Smith almost 4 years ago

  • Status changed from Assigned to Closed

All done. Also set upper range of the new QAQCRATIO variables set to 10, and added reading to the ArPurity panel.